It is necessary to plan a buffer space to absorb the fast pressure variations, especially the solenoid valves situated after a B type regulator. The piping volume, from the regulator to the consumption point, has to be at least equal:
- in BP (21, 27, 37 mbar) to the 1/500 of the regulator nominal flow
- in MPA (300 mbar) to the 1/1000 of the regulator nominal flow
|
Designation
|
Fitting double female
|
2 transition fittings pressure gauge
|
Ref. Chuchu
|
|
Tank 10 L
|
1"1/4
|
1/4"
|
2420-010
|
|
Tank 25 L
|
1"1/2
|
1/4"
|
2420-025
|
|
Tank 50 L
|
1"1/2
|
1/4"
|
2420-050
|
Maximal use pressure: 500 mbar.
Buffer tank horizontal or vertical assembly - Delivered with caps on the 2 transition fittings.
|